Specifications

2 SOFT MONITOUCH TELLUS
2-22
Monitored device write protection setting
For the V series
1) Open the V-SFT screen data.
2) From the [System Setting] menu, select [Network Table Setting] and then [Ethernet]. The network
table edit screen is opened.
3) Double-click the number to which the IP address of the V series is set. The [Set Network Table]
dialog box is displayed.
4) Clear the checkmarks for [Memory Protect].
For TELLUS (HMI)
1) Open the [Option] dialog box.
2) Click the [Detail Setting] button under [Ethernet]. The [Ethernet Detail Setting] dialog box is
displayed.
3) Clear the checkmarks for [Memory Protect].
With [Use Network Table] checked, proceed to changing the network table edits for V-SFT screen data.