Q12 I click a switch on the screen in the remote mode, but the data is not written to the
MONITOUCH or PLC.
A12 Check the memory type of the target to which data is written.
If system memory $s/$T is used, writing from the remote-mode screen to the monitored device is not
possible.
If memory except for $s/$T is used, the target is write-protected. Cancel the protection.
Write protection is set on V-Server. In the case of internal memory or memory card memory, the options of
[Memory Protect] are included in the screen data for individual monitored devices.
Memory available with remote monitor
V-Server write protection setting
Procedure
1) Select the monitored device to which writing is impossible from V-Server.
2) From the [Edit] menu, select [Remote Monitor Setting]. The [Remote Monitor Setting] dialog box is
displayed.
3) Clear the checkmark for [Write Protect].
Memory Read Write* Remarks
PLC memory, I/O memory Writing is not allowed if the read-only setting is
specified for the PLC.
Internal memory
$u/$L/$LD
$s/$T Remote PC's internal memory
Memory card memory
Temperature controller memory Writing is not allowed if it is read-only type
memory.