Specifications

2 SOFT MONITOUCH TELLUS
2-9
2
Q7 Connection with YOKOGAWA FA-M3 via Ethernet cannot be established.
A7 Check the settings below.
Screen data
From [Select PLC Type], select [FA-M3 (Ethernet)].
Register the PLC in the network table.
IP address: Match the IP address to the setting on the Ethernet unit for the PLC.
Port No.: 12289 (Fixed according to the PLC specifications)
Others: Set the default gateway and subnet mask appropriately for the network.
For PLC
Set an IP address of the PLC on the Ethernet unit (using the switches on the side).
SW1 - SW8: Used for IP address setting
•SW9:
Wiring (for 10Base-T)
1:1 connection (without hub)
Use a cross cable.
1:1 connection (with hub) or 1:n connection
Use a straight cable.
No. ON/OFF
1: DATA CODE ON: BINARY
2: PROTECTION OFF
3: OFF
4: OFF
5: OFF
6: OFF
7: TCP CONNECTION ON TIMEOUT ERROR OFF: CLOSE
8: MODE OFF: NORMAL
For information on AUI connection, refer to the PLC Connection Manual or the instruction manual for
the PLC.