Specifications
2 SOFT MONITOUCH TELLUS
2-9
2
Q7 Connection with YOKOGAWA FA-M3 via Ethernet cannot be established.
A7 Check the settings below.
Screen data
• From [Select PLC Type], select [FA-M3 (Ethernet)].
• Register the PLC in the network table.
IP address: Match the IP address to the setting on the Ethernet unit for the PLC.
Port No.: 12289 (Fixed according to the PLC specifications)
Others: Set the default gateway and subnet mask appropriately for the network.
For PLC
Set an IP address of the PLC on the Ethernet unit (using the switches on the side).
• SW1 - SW8: Used for IP address setting
•SW9:
Wiring (for 10Base-T)
♦ 1:1 connection (without hub)
• Use a cross cable.
♦ 1:1 connection (with hub) or 1:n connection
• Use a straight cable.
No. ON/OFF
1: DATA CODE ON: BINARY
2: PROTECTION OFF
3: OFF
4: OFF
5: OFF
6: OFF
7: TCP CONNECTION ON TIMEOUT ERROR OFF: CLOSE
8: MODE OFF: NORMAL
For information on AUI connection, refer to the PLC Connection Manual or the instruction manual for
the PLC.