User's Manual
Table Of Contents
- 1. Getting started
- 2. Introduction
- 3. Preparation
- 4. About the terminal
- 5. Mounting and installing the terminal
- 6. Connecting to the terminal
- 7. Managing the terminal
- 8. Configuring the terminal
- 9. Configuring the traffic interfaces
- 10. Cross Connections
- Embedded cross connect switch
- The Cross Connections application
- The Cross Connections system requirements
- Installing the Cross Connections application
- Opening the Cross Connections application
- The Cross Connections page
- Setting the terminal's address
- Management and user ethernet capacity
- Setting card types
- Getting cross connection configuration from the terminals
- Creating cross connections
- Sending cross connection configuration to the terminals
- Saving cross connection configurations
- Using existing cross connection configurations
- Printing the cross connection configuration
- Deleting cross connections
- Configuring the traffic cross connections
Mounting and installing the terminal | 34
12 VDC cable
The 12 VDC power supply is supplied with a 3 metre red/black cable of two pairs of 2.3 mm
2
(72
strands of 0.2 mm
2
) making a total of 4.6 mm
2
per connection. This increase in wire size is to carry the
increased current consumption of the 12 VDC supply (max 18 Amps per terminal).
This 3 metre cable is engineered to power a fully loaded terminal from a 12 VDC supply. A longer
cable should not be used as the additional voltage drop could cause the power supply to fail.
If longer cable runs are required between the 12 VDC power supply and the terminal, it is suggested
that high current distribution bus bars are used to feed the rack and the supplied power cable used
between the bus bars and the terminals.
Terminal Power input Cable colour
+V Positive DC input Red
-V Negative DC input Black
1. Fit both pairs of lugs into the terminal screw
clamps.
2. Twist the other ends together when fitting
to the source.