Product Description
Scotch™ 130C Electrical Tape is a highly conformable
linerless Ethylene Propylene Rubber (EPR), high voltage
insulating tape formulated to provide excellent thermal
dissipation of splice heat. The tape is designed for use in
splicing and terminating wires and cables. Rated up to
90°C continuous operating temperatures and short term
130°C overload service. The tape will meet industry
specifications for flame retardance and has excellent
physical and electrical properties which provide
immediate moisture seals and void-free buildups. This
product can be used for low – and high – voltage (up to
69 kV) applications.
Tape Features
Linerless, self-bonding primary insulating tape rated
up to 69 kV.
High thermal conductivity.
Ethylene propylene base.
Flame retardant.
Excellent physical and electrical properties.
Designed to insulate splices and terminate cables
whose overload temperatures can reach 130°C.
Physical and electrical properties unaffected by
degree of stretch.
Physical and electrical properties unaffected by
solvents normally used when splicing high-voltage
cables.
Compatible with common solid dielectric cable
insulation.
Uniform tape unwind from roll.
Small roll size (OD)
Five year shelf life.
Stable over wide applications temperature range.
Weather resistant.
Applications
Primary insulation for splicing all types of solid
dielectric insulated cables up to 69 kV.
Primary insulation for building stress cones on all
types of solid dielectric insulated cables up to 35 kV.
Jacketing (secondary insulation) on high-voltage
splices and terminations.
Moisture sealing electrical connections.
Bus bar insulations.
End sealing high-voltage cables.
Motor leads.
Jacket repairs.
Data – Physical and Electrical Properties
Physical Properties
Test Method Typical Value*
Colour Black
Thickness ASTM D-4325 0.762 mm
Tensile Strength ASTM D-4325 1.72 Mpa
Ultimate Elongation ASTM D-4325 1000%
Operating Temperature ASTM D-4388 90°C
Emergency Overload ASTM D-4388 130°C
Thermal Resistivity 300°C
3M Transient cm/watt
Ozone Resistance ASTM D-4388 Passes
Heat Resistance ASTM D-4388 Passes
UV Resistance ASTM D-4388 Passes
Flame Resistance Passes
IEEE Std 27-1974 ANSI
C37.20C 74
Electrical Properties
Test Method Typical Value*
Dielectric Strength ASTM D-4325
Original 29.5 MV/m
24 hrs in H
2
O 29.5 MV/m
96 hrs @ 23°C 28.7 MV/m
96% RH
Volume Resistivity ASTM D-4325
Original >10
15
ohm-cm
Aged 96 hrs @ 23°C 96% RH >10
14
ohm-cm
Insulation Resistance >10
6
M ohms
Dielectric Constant ASTM D-4325
1200 volts @ 60 Hz
23°C 3.5
90°C 3.6
Dissipation Factor ASTM D-4325
1200 volts @ 60 Hz
23°C 0.70%
90°C 3.00%