Drawing

Table Of Contents
3M™
Medium-Wall Heat Shrink Tubing IMCSN
3 of 5
3M™ IMCSN Selection Guide
Note: 3M IMCSN tubing is supplied in 48-inch lengths with adhesive. Uncoated products available on special order.
Product Number
Cable Size Range
Minimum Expanded/
Maximum Recovered I.D.
Cable O.D. Use Range
Maximum - Minimum
IMCSN-0400-48A
12 - 6 AWG
(4 - 10 mm
2
)
0.40 / 0.15”
(10,2 / 3,8 mm)
0.35 - 0.15”
(8,8 - 3,8 mm)
IMCSN-0800-48A
8 - 3 AWG
(10 - 25 mm
2
)
0.80 / 0.22”
(20,3 / 5,6 mm)
0.70 - 0.22
(18 – 5,6 mm)
IMCSN-1100-48A
2 - 2/0 AWG
(35 - 60 mm
2
)
1.10 / 0.37”
(27,9 / 9,4 mm)
0.95 - 0.37
(24 9,4 mm)
IMCSN-1300-48A
1 - 4/0 AWG
(50 - 100 mm
2
)
1.30 / 0.43”
(33,0 / 10,9 mm)
1.10 - 0.43
(28 - 10,8 mm)
IMCSN-1500-48A
1/0 - 250 kcmil
(60 - 120 mm
2
)
1.50 / 0.50”
(38,1 / 12,7 mm)
1.30 - 0.50
(33 12,1 mm)
IMCSN-1700-48A
4/0 - 400 kcmil
(120 - 200 mm
2
)
1.70 / 0.60”
(43,2 / 15,2 mm)
1.45 - 0.60
(37 15,2 mm)
IMCSN-2000-48A
300 - 500 kcmil
(185 - 250 mm
2
)
2.00 / 0.75
(50,8 / 19,1 mm)
1.75 - 0.75”
(44,5 19,0 mm)
IMCSN-3000-48A
600 - 1250 kcmil
(325 - 625 mm
2
)
3.00 / 1.00
(76,2 / 25,4 mm)
2.50 1.00
(63,5 25,4 mm)
IMCSN-4300-48A
1000 - 2500 kcmil
(625 - 1000 mm
2
)
4.30 / 1.50
(109,2 / 38,1 mm)
3.60 1.50
(91,5 38,1 mm)
Performance Tests
Meets MIL-I-23053/15A Class 2.
Property
Requirement*
Test Results
Corrosion
(16 hours @ 121°C)
- Copper Mirror
- Copper Contact
No corrosion
No corrosion or pitting
Pass
Pass
Flammability
(Five 15-second Bunsen
burner applications)
Nonburning
Pass
Water Absorption
(24 hours @ 25°C)
0.5% Maximum
weight increases
0.02%
Heat Aging
(7 days @ 175°C)
- Ultimate Elongation
- Tensile Strength
100% Minimum
1000 psi Minimum
225%
1820 psi
Fungus Resistance
Non-nutrient Pass
Shelf Life
Storage @ 40°C for 2 years
With maintenance of dimensions
Pass
*Based on MIL-I-23053/15A Class 2