3M™ Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit With High-K Stress Relief For Tape Shield, Wire Shield and UniShield® Cable 7622-T-110, 7623-T-110, 7624-T-110, 7625-T-110, 7626-T-110 Instructions IEEE Std. No. 48 Class 1 Termination 15 kV Class 110 kV BIL F CAUTION Working around energized systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling electrical equipment.
1.0 Kit Contents 3 High–K, Tracking Resistant, Silicone Rubber Terminations 3 Pre-formed Ground Braids 3 Constant Force Springs 3 3M™ EMI Copper Foil Shielding Tape 1181 Strips, 1/2" x 10" 6 Strips Scotch® Mastic Strip 2230 (black with white release liners, bagged) 1 3M™ Cable Cleaning Preparation Kit CC-2 1 Instruction Sheet Note: Do not use knives to open plastic bags. Kit Selection Table NOTE: Final Determination Factor is cable insulation diameter.
2.0 Instructions for Tape Shielded Cable Prepare Cable 2.1 Check to be sure cable size fits within kit range as shown in Table 1. 2.2 Prepare cable using dimensions shown in Figure 1. BE SURE TO ALLOW FOR DEPTH OF TERMINAL LUG. If necessary to prevent tape shield from unrolling, hold down edge with a single wrap of 3M™ EMI Copper Foil Shielding Tape 1181.
3.2 Position pre-formed ground braid with short tail over tape shield directly adjacent to cable jacket cut edge. PLEASE NOTE: The ground braid needs to make full contact with the metallic tape shield. Position long tail of ground braid, extending over cable jacket with solder block over mastic strip (Figure 3). Secure ground braid to cable jacket 4-1/2" (114 mm) from cable semi-con edge using vinyl tape (Figure 3).
3.5 Wrap two highly stretched half-lapped layers of electrical grade vinyl tape around Scotch® Mastic Strip 2230, constant force spring and exposed tape shield (Figure 5). NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 1" (25 mm) must be exposed.
.0 Install Termination 6.1 Slide the termination body onto the cable and remove core. Make sure the termination body (not the core) is butted up to the edge of the vinyl tape marker previously applied (Figure 7). Pull the core while unwinding, counterclockwise, starting with the loose end (Figure 7). Be sure to alternate the pulling and unwinding actions (pullunwind-pull-unwind-etc.) to help prevent the core material from binding up as the core is being removed.
Instructions for Wire Shielded Cable 7.0 Prepare Cable 7.1 Check to be sure cable size fits within kit range as shown in Table 1. 7.2 Prepare cable using dimensions shown in Figure 8 and Figure 9. BE SURE TO ALLOW FOR DEPTH OF TERMINAL LUG.
.0 Install Ground Braid 8.1 Select a Scotch® Mastic Strip 2230 from kit and remove white release liners. Using light tension apply a SINGLE WRAP of mastic around the cable jacket 1/4" (6 mm) from cut edge (Figure 10). Cut off excess. 1/4" (6 mm) Semi-Con 1st Scotch Mastic Strip 2230 ® Cable Jacket Figure 10 8.2 Position pre-formed ground braid with short tail over wire shield directly adjacent to cable jacket cut edge.
8.3 Wrap ground braid around cable shield wires one complete wrap, trim excess to prevent overlap and secure in place with constant force spring. Wrap spring in same direction as ground braid (Figure 12). Cinch (tighten) the spring after wrapping the final winding. 8.4 Select second Scotch® Mastic Strip 2230 from kit and remove white release liners. Apply a second SINGLE WRAP of mastic over solder block on ground braid and previously applied mastic (Figure 12). Cut off excess.
9.0 Install Lug or Connector Important Packaging Notice In order to make sure that you receive an undamaged termination, this 3M™ Cold Shrink QT-III Termination is packed with a RED SHIPPING CORE inside of the white core. Please remove the red shipping core BEFORE you install the termination. This shipping core can be recycled with other polypropylene waste 9.1 Check to insure 3M™ Cold Shrink QT-III Silicone Rubber Termination fits over the selected lug or connector.
.2 Connect ground braid to system ground according to standard practice. Correct Installation of Termination on Wire Shielded Cable Vinyl Tape Marker Ridge at End of Cable Insulation Shield (Semi-Con) Ridge at End of High-K Tube Cable Insulation Semi-Con Insulation Shield Environmental Top Seal Conductor Stress Controlling Compound High-K Stress Relief Tube Instructions for UniShield® Shielded Cable 12.0 Prepare Cable 12.1 Check to be sure cable size fits within kit range as shown in Table 1. 12.
.4 Remove constant force spring. Bend shield wires back upon cable jacket 1-1/2" (38 mm). Cut excess shield wire and discard (Figure 17). Depth Of Terminal Lug + Growth Allowance 9" (229 mm) 1-1/2" (38 mm) Semi-Conductive Jacket Fold Back Shield Wires Figure 17 12.5 Remove semi-conductive jacket to dimension shown in Figure 18. NOTE: To ease jacket removal, install constant force spring as shown in Figure 18 and ring-cut 80% through jacket.
.0 Install Ground Braid 13.1 Select a Scotch® Mastic Strip 2230 from kit and remove white release liners. Using light tension apply a SINGLE WRAP of mastic around the cable semi-conductive jacket 1/4" (6 mm) from shield wires (Figure 19). Cut off excess. 1/4" (6 mm) Semi-Con Shield Wires 1st Scotch® Mastic Strip 2230 Figure 19 13.2 Position pre-formed ground braid with short tail directly over cut edge of folded back shield wires.
Constant Force Spring Shield Wires Ground Braid Trim 1st Scotch Mastic Strip 2230 ® Solder Block Cable Wire Shield 2nd Scotch® Mastic Strip 2230 Ground Braid Leg Figure 21 13.5 Wrap two highly stretched half-lapped layers of electrical grade vinyl tape around mastic seal, constant force spring and exposed shield wires (Figure 22). NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 1" (25 mm) must be exposed.
NOTE: Refer to pages 17-19 for 3M ™ connector and lug crimping information. NOTE: For Aluminum Conductors - Thoroughly wire brush conductor strands to remove aluminum oxide layer. Insert conductor into lug or connector and then remove conductor. This will transfer some of the antioxidant compound onto the conductor. Wire brush the anti-oxidant paste into the strands. Immediately insert conductor into lug or connector barrel as far as it will go.
Correct Installation of Termination on UniShield® Shielded Cable Vinyl Tape Marker Ridge at End of Cable Insulation Shield (Semi-Con) Ridge at End of High-K Tube Semi-Con Cable Insulation Stress Controlling Compound Conductor Environmental Top Seal High-K Stress Relief Tube 16 78-8113-5099-6 Rev E
Tooling Index Lug and Crimping Information for 3M™ Scotchlok™ Copper Lugs 30014 thru 30045 One hole 31145 thru 31178 Two hole-long barrel 31036 thru 31068 One hole-long barrel Cable Size AWG/ kcmil Stud Size (in.) 3M™ Scotchlok™ Copper Lug Number 6 10 1/4 5/16 4 Crimping Tool-Die Sets (Minimum Number Of Crimps) Burndy Corporation Thomas & Betts Corporation Square D Co. Anderson Div.
Tooling Index Lug and Crimping Information for 3M™ Scotchlok™ Copper/Aluminum Lugs 40016 thru 40079 One hole 40132 thru 40178 Two hole Cable Size AWG/ kcmil Stud Size (in.
Tooling Index Crimping Information for 3M™ Stem Connectors Copper/Aluminum Conductor Size AWG & kcmil Stranded 2, 1 4 1/0 2/0 3/0 4/0 Solid 1, 1/0 2 2/0 3/0 4/0 – Crimping Table For 3M™ Stem Type Connector 3M Connector Number Recommended Crimping Tools ™ SC0001 SC0002 SC0010 SC0020 SC0030 SC0040 Manufacturer Mech. Tool Die (Minimum No. Crimps) Hydraulic Die (Minimum No.
3M, Scotch and Scotchlok are trademarks of 3M Company. UniShield is a trademark of General Cable Technologies Corporation. Important Notice All statements, technical information, and recommendations related to 3M's products are based on information believed to be reliable, but the accuracy or completeness is not guaranteed. Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all risks and liability associated with such use.