Cut Sheet
Description Amperes
Continuous 200 A rms
Switching 10 operations at 200 A rms at 14.4 kV
Fault Closure 10,000 A rms symmetrical at 14.4 kV
after 10 switching operations for 0.17 s
Short Time 10,000 A rms symmetrical for 0.17 s
3,500 A rms symmetrical for 3.0 s
Current ratings and characteristics are in accordance with ANSI/IEEE
Standard 386.
Table 2
Current Ratings and Characteristics
2.0 Features and Detailed Description
Figure 2.
Elbow cutaway illustrates design integrity.
Figure 3.
Elbow profile and stacking dimensions as referenced in
ANSI/IEEE Standard 386.
Note: Dimensions are given
for reference only.