Cut Sheet
Cold Shrink
5732–5735 Low Voltage Inline Splice Kits
Instructions
For use with 3/C Armor Power
Cable (TECK-90) up to 1000 Volts
Kit Contents:
3 Cold Shrink PST Tubes
1 Cold Shrink PST Jacket Tube
2 Scotch
®
Shielding Tape 24 Strips
1 Copper Shielding Sleeve (2' Lg.)
2 Constant Force Springs (Size #4)
NOTE: Connectors are not included in kit. Use only
CSA certified compression connectors.
Table 1: Kit Selection
1.0 Prepare Cable
See Table 2 for cable cutback dimensions.
1.1 Position cables and cut so conductor ends overlap.
(See Fig. 1)
1.2 Remove cable jacket of each cable according to
dimension “D”. (See Fig. 1)
1.3 Remove armor leaving 1" of armor exposed from end
of each cable jacket. (See Fig. 1)
1.4 File rough edges of armor smooth.
1.5 Remove inner jacket leaving
1
⁄
2
" exposed from the end
of the armor.
1.6 Remove cable fillers back to end of inner jacket.
1.7 Match conductor phases.
1.8 Shorten conductors by dimensions indicated in Fig. 1.
1.9 Remove insulation from conductor ends:
— If using Copper connectors: Remove insulation for
1
⁄
2
of connector length.
— If using Aluminum connectors: Remove insulation
for
1
⁄
2
of connector length +
1
⁄
4
".
Fig. 1 Cable Preparation
Table 2: Dimensions for Fig. 1
Kit Cable Sizes Overall Jacket
No. AWG or MCM Diameter
5732 #2—1/0 0.95—2.4"
(24—61 mm)
5733 2/0—250 1.15—3.3"
(29—84 mm)
5734 250—500 1.55—4.0"
(39—102 mm)
5735 500—750 1.55—4.0"
(39—102 mm)
Kit No. A B C D
5732 19" 4.5" 7" 13"
(48.5 cm) (11.5 cm) (18 cm) (33 cm)
5733 22" 5.5" 8" 15"
(56 cm) (14 cm) (20.5 cm) (38 cm)
5734 & 5735 26" 6.5" 10" 18"
(66 cm) (16.5 cm) (25.5 cm) (45.5 cm)
CAUTION
Working around energized electrical systems may cause
serious injury or death. Installation should be performed
by personnel familiar with good safety practice in handling
electrical equipment. De-energize and ground all electrical
systems before installing product.
CSA Certified for
600V or Less