Cut Sheet
266 FAX: 800-245-0329
Single Core Tape Shield, Wire Shield & UniShield® Cable, 5–46 kV: 3M™ Cold Shrink QT-II Terminations: Indoor Kits
3M™ Cold Shrink QT-II Termination Kit 5620K Series for 5-15 kV
3M™ Cold Shrink QT-II Silicone Rubber Termination Kits 5620K Series contain one-piece, nonskirted, silicone rubber terminations, qualified as IEEE
Standard 48 Class I for weather-protected applications. Termination assemblies consist of a high dielectric constant (Hi-K) stress control tube insulated with
a nontracking silicone rubber insulator, prestretched and loaded together onto a removable core. The kits are designed for terminating solid dielectric
shielded power cable rated 5–15 kV, with tape shield, wire shield and UniShield® constructions.
Each kit contains sufficient material to make 3 single-phase terminations. Lugs must be ordered separately.
Number of Conductors
Single Conductor
Shielding Type
Tape Shield, Wire Shield, UniShield®
Indoor/Outdoor
Indoor
Breakout Boot
No
Insulation Rejacketing
No
No. Skirts
0
Voltage
5 kV, 8 kV, 15 kV
Packaging
1 kit per case (three single-phase ter-
minations per kit)
Order No. UPC BIL
Max. Installed
Length
Insul. O.D. Range Cond. Size 5 kV 100%
Cond. Size 5
kV 133% / 8
kV 100%
Cond. Size 8
kV 133%
Cond. Size 15
kV 100%
Cond. Size 15
kV 133%
5621K 054007-
12250
110 kV 9.5"
(241 mm)
0.32"-0.46"
(8,1-11,7 mm)
8-4 AWG
(10-16 mm²)
8-6 AWG
(10-14 mm²)
8 AWG
(10 mm²)
--
5622K 054007-
12251
110 kV 9.5"
(241 mm)
0.44"-0.65"
(11,2-16,5 mm)
2-2/0 AWG
(35-60 mm²)
4-1/0 AWG
(22-50 mm²)
6-1 AWG
(14-38 mm²)
--
5623K 054007-
12252
110 kV 11.0"
(279 mm)
0.56"-0.87"
(14,2-22,1 mm)
2/0 AWG-250 kcmil
(70-120 mm²)
1/0-4/0 AWG
(60-100 mm²)
1-3/0 AWG
(50-80 mm²)
4-2/0 AWG
(22-60 mm²)
4-1 AWG
(22-38 mm²)
5624K 054007-
12254
110 kV 11.0"
(279 mm)
0.78"-1.30"
(19,8-33,0 mm)
300-750 kcmil
(185-325 mm²)
250-750 kcmil
(150-325 mm²)
4/0 AWG-600
kcmil
(120-300 mm²)
2/0 AWG-500
kcmil
(70-250 mm²)
1 AWG-350
kcmil
(50-150 mm²)
5625K 054007-
12255
110 kV 11.0"
(279 mm)
1.09"-1.80"
(27,7-45,7 mm)
600-1500 kcmil
(325-725 mm²)
600-1500
kcmil
(325-725 mm²)
500-1250
kcmil
(300-625 mm²)
500-1250
kcmil
(300-625
mm²)
350-1000
kcmil
(185-500
mm²)
Medium Voltage Terminations, 5–46 kV