Drawing
3. Specifications
Product
Installations shall be in strict accordance with manufacturer’s written instructions, as shown on approved shop
drawings. The device shall also be classified by Underwriter’s Laboratory Inc. as a through-penetration firestop
device when tested in accordance with ASTM E 814 (UL 1479) for up to 3 hour rating.
All penetrations must be firestopped with a UL Classified system or device as listed in current UL Fire
Resistance Directory or have approved shop drawing prior to installation. Suitability for the intended service
application should be determined prior to installation.
4. Performance
A. Testing Procedures
•
Tested per ASTM E 814 (UL 1479)
•
UL classified 1, 2 and 3 hour fire (F) and temperature (T) rating.
See UL Directory under through-penetration firestop devices.
•
UL classified L rating, Hot and Cold Smoke Seal. See UL
Directory under through-penetration firestop devices.
•
ULC
5. Installation Techniques
•
Prepare the opening by cutting correct size hole
•
Slide the device either over existing
penetrants or into the opening
•
Remove the foam visual/smoke seals and place in a safe location
•
Secure with optional 3M
™
Fire Barrier Pass-Through Mounting
Brackets, 3M
™
Fire Barrier Pass-Through Stud Brackets and/or
3M
™
Fire Barrier Sealant to the assembly
•
Install penetrants
•
Re-install the foam visual/smoke seals flush with device ends
6. Re-installing Penetrations
•
Remove the foam visual/smoke seals and place in a safe location
•
Install new penetration
•
Re-install the foam visual/smoke seals flush with device ends
7.
Maintenance
The 3M Fire Barrier Pass-Through Device requires no
maintenance over a normal life cycle.
8. Availability
3M Fire Barrier Pass-Through Devices are available from
Authorized 3M Fire Protection Products Distributors.
Call 1-800-328-1687 opt. 1
Warranty and Limited Remedy. This product will be free from defects in material and manufacture for a period of ninety (90) days from date of purchase. 3M MAKES NO OTHER
WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. User is responsible for
determining whether the 3M product is fit for a particular purpose and suitable for user's application. If this 3M product is defective within the warranty period stated above, your exclusive
remedy and 3M's sole obligation shall be, at 3M's option, to replace or repair the 3M product or refund the purchase price of the 3M product.
Limitation of Liability. Except where prohibited by law, 3M will not be liable for any loss or damage arising from this 3M product, whether direct, indirect, special, incidental or
consequential, regardless of the legal theory asserted, including warranty, contract, negligence or strict liability.
New
3) Secure in wall
with sealant and/or
mounting bracket.
2) Slide device into wall or floor
.
Ne
xt, install penetration
and insert foam seal.
1) Prepare opening.
2) Slide device into wall or floor
.
Next, install penetration
and insert foam seal.
3) Secure in wall
with sealant and/or
mounting bracket.
1) Prepare opening.
New
Printed in U.S.A. 3M is a trademark of 3M. 98-0213-4337-5©3M 2007.
Retro Fit
3) Secure in wall with sealant and/or
mounting bracket then insert foam seal.
2) Close cover and slide into wall assembly.
1) Insert around penetration(s) optional.
3) Secure in wall with sealant and/or
mounting bracket then insert foam seal.
2) Close cover and slide into wall assembly.
1) Insert around penetration(s) optional.
Retro Fit
Building and Commercial
Services Division
3M Center
Building 223-2N-21
St. Paul, MN 55144-1000
800-328-1687
www.3m.com/firestop