Cut Sheet
3M™ Motor Lead Splicing Kits 5300 Series
2 of 4
Kit Contents
Each kit contains sufficient quantities of the following materials to make three splices
(lugs and vinyl tape are not included), see chart below.
Kit Component
Kit Number
5300
Thru
5301
5302
Thru
5394
5311
Thru
5314
5316
Thru
5319
5321
Thru
5324
5331
Thru
5333
Lug covers (pigtail) X X X X
Locking Pins X X
Splice Cover (inline) X
PST Cold Shrink Tubes X X
Adapter Sleeves X X
Scotch® Electrical Stress Control Tape 2220 X X
Scotch® Linerless Rubber Tape 130C X X X
Mastic Sealing Strips X X X X
Solvent Cleaning cloths X X X
Silicone Grease Lubricant X X X X X X
Instruction Sheet X X X X X X
Applications
3M™ Motor Lead Splicing Kits 5300 Series can be used on cables with a rated operating
temperature of 90°C and an emergency overload rating of 130°C. Splicing kits 5300
through 5314 are rated for 1000 Volts, and kits 5316 through 5334 are rated for 5/8 kV.
To splice (insulate and seal) motor lead connections for:
1000 Volts and less cables sized 16 AWG to 500 kcmil
5/8 kV shielded and non-shielded feeder cables sized 8 AWG to 500 kcmil
Polyethylene cable
Cross linked polyethylene cable (XLP)
Ethylene propylene rubber cable (EPR)
Copper conductors
Typical Properties
Physical Properties (Test Method)
(ASTM D-412 unless otherwise noted)
Typical Value
US units (metric)
Color
Black
300 Modulus
480 psi (3,3 MPa)
Ultimate Tensile Strength
1400 psi (9,6 MPa)
Ultimate Elongation
750%
Die C Tear (ASTM D-624C)
150 ppi (26,3 KN/m)
Electrical Properties (Test Method)
(ASTM D-149)
Typical Value
US units (metric)
Dielectric Strength
Original
7 days in H
2
O, 90°C (194°F)
365 V/mil (14,3 MV/mil)
282 V/mil (11,1 MV/m)
*All values are averages and are not intended for specification purposes.