User's Manual
User Manual
Fire ID TM-801-EN
17
5.1. Manufacturer’s Declaration- Electromagnetic Emission
The Fire ID system is intended for use in the electromagnetic environment specified below. The
customer or the user of Fire ID system should assure that it is used in such an environment
Emission test Compliance Electromagnetic environment - guidance
RF emissions
CISPR 11
Group 1
Class B
The Fire ID system uses RF energy only for its
internal function. Therefore. Its RF emissions are
very low and are not likely to cause any
interference in nearby electronic equipment
5.2. Manufacturer’s Declaration - Electromagnetic Immunity
The Fire ID system is intended for use in the electromagnetic environment specified below. The
customer or the user of Fire ID system should assure that it is used in such an environment
Immunity test
IEC 60601
Test level
Compliance level
Electromagnetic
Environment -guidance
Conducted RF
IEC 61000-4-6
3 Vrms
150 kHz to 80 MHz
3 Vrms
150 kHz to 80 MHz
Portable and mobile RF
communications equipment
should be used no closer to
any part of the Fire ID system,
including cables, than the
recommended separation
distance calculated from the
equation applicable to the
frequency of the transmitter.
Recommended separation
distance