Powerware Uninterruptible Power System Installation and Operator's Manual
67
Powerware
®
PrestigeSeriesInstallation andOperator’s ManualforIBMApplications (3000 VA)Uncontrolled Copy
CHAPTER 6
SPECIFICATIONS
3000 VA Model Specification with PPDM
V
o
l
t
a
g
e
I
n
:
O
u
t
In
p
ut
OutputCurrent
Voltage In:Out
I
n
p
u
t
Current
O
u
t
p
u
t
C
u
r
r
e
n
t
(Totalnottoexceed2000 Watts, 3000 VA)
208:120/208
13.0A 12.50A/14.40A
208:120/240 13.0A 12.50A
240:120/240 11.3A 12.50A
208:120 13.0A 12.50A (2x5-15R)/25.00A (L5-30R)
240:120 11.3A 12.50A (2x5-15R)/25.00A (L5-30R)
220:220 12.3A 13.64A
230:230 11.7A 13.04A
240:240 11.3A 12.50A
Prestige 3000 UPS Physical Specifications
Parameter UPS Cabinet BatteryCabinet PowerPassDistribution Module
Height 252 mm (9.91”) 252 mm (9.91”) 252 mm (9.91”)
Width 142.5 mm (5.61”) 142.5 mm (5.61”) 142.5 mm (5.61”)
Depth 400 mm (15.75”) 400 mm (15.75”) 400 mm (15.75”)
Weight 7.4 kg (16.25 lb) 23.6 kg (52 lb) 21.4 kg (47 lb)