10. Turn on the equipment that is connected to the UPS.
11. Press and hold the Output
On button until you hear the UPS
beep (approximately one second).
The indicator remains lit and the Self Test indicator turns
on. The front panel displays the percentage of full load being
applied to the UPS. The UPS is now in Normal mode with the
load online. See “Normal Mode” on page 48 for more
information.
REPO Installation
WARNING
Onlyqualifiedservice personnel (suchasa licensedelectrician)shouldperform the
hardwired installation.
The REPOswitch is a customer-supplied switch thatcan disconnect UPS
output voltage from your protected equipment. If you are using a REPO
switch, you need a junction box, external wiring, and a switch with the
following specifications:
The switchshould be a wall-mounted, momentary-contact, normally
open, pushbutton switch.
Minimum ratings of 240 Vac and 35 mA.
Wire should be 18 AWG (0.75 mm
2
) minimum.
CAUTION
TheblackandwhiteREPOwiresareat high-voltagepotential(240V).Refer toyour
localelectricalcodefor properinstallation ofthe high-voltage REPOwires.
To ensurethe UPS stops supplyingpower tothe loadduring anymode of
operation,the input powermust bedisconnectedfrom theUPS when the
emergencypower-offfunction is activated.