Access the address switches 1

Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, NY 14450
USA
www.boschsecurity.com
© 2013 Bosch Security Systems, Inc. F01U.265.451 | 03 | 2013.08
Copyright
This document is the intellectual property of Bosch Security
Systems, Inc. and is protected by copyright. All rights reserved.
Trademarks
All hardware and software product names used in this
document are likely to be registered trademarks and must be
treated accordingly.
Bosch Security Systems, Inc. product manufacturing dates
Use the serial number located on the product label and refer to
the Bosch Security Systems, Inc. website at
http://www.boschsecurity.com/datecodes/.
10 | Speci cations
Dimensions 6.2 in x 4.7 in x 1 in
(158 mm x 120 mm x 26 mm)
Voltage (input) 12 VDC nominal
Current 35 mA in standby mode
80 mA in alarm mode
Operating temperature 0°C to +50°C (+32°F to +122°F)
Relative humidity 5% to 93% at +32°C (+90°F) non-
condensing
Terminal wire size 12 AWG to 22 AWG (2 mm to 65
mm)
SDI2 wiring Maximum distance - wire size
(unshielded wire only):
1000 ft (305 m) - 22 AWG (0.65
mm)
Compatibility B5512
B4512
B3512
D9412GV4 version 2.00 or higher
D7412GV4 version 2.00 or higher
9 | Certi cations
Region Certi cation
US UL 365 - Police Station Connected Burglar Alarm
Units and Systems
UL 609 - Local Burglar Alarm Units and Systems
UL 985 - Household Fire Warning System Units
UL 1023 - Household Burglar-Alarm System Units
UL 1076 - Proprietary Burglar Alarm Units and
Systems
UL 1610 - Central Station Burglar Alarm Units
CSFM - California Of ce of The State Fire
Marshal
FCC Part 15 Class B
CA Canada CAN/ULC S303 - Local Burglar Alarm
Units and Systems
CAN/ULC S304 - Signal Receiving Centre and
Premise Alarm Control Units
ULC-ORD C1023 - Household Burglar Alarm
System Units
ULC-ORD C1076 - Proprietary Burglar Alarm
Units and Systems
ICES-003 - Digital Apparatus
Showing the keypad rmware version:
1. Remove the keypad from the base to remove power to the
keypad. Refer to Figures 2.1 and 2.2.
2. Return the keypad to the base to restore power.
The keypad shows the
model number, keypad address, and
rmware version for 10 sec.
8 | Show the rmware version
NOTICE!
You can also view a keypad’s rmware version in RPS.
The control panel supervises all keypads on the SDI2 bus.
If a supervised keypad fails to respond to the control panel,
the control panel declares a Missing Keypad Trouble. When
the control panel can again communicate with the keypad,
it restores the Missing Keypad Trouble. During a Missing
Keypad Trouble, any connected keypad that maintained
contact with the control panel shows the Missing Keypad
Trouble as its idle text, and shows the missing keypad’s
address. The communicating keypads also sound a trouble
tone. Users can silence the trouble tone. If no other troubles
exist, the tone silences when the missing keypad restores.
7 | Supervision
6 | Audible tones
The keypad has a built-in speaker that produces several distinct
warning tones. The keypad backlight illuminates when it emits
an audible tone.
Tone Description
Fire signal When an area is in re alarm, the keypad
emits a pulsed, high-pitched bell tone.
Gas signal When a gas point activates, the keypad
emits a unique high pitched tone.
User alarm When a user alarm (such as panic and
medical alarms) occurs, the tone sounds
for the programmed amount of time.
Burglary signal When an area is in alarm, the keypad
emits a steady, high pitched bell tone.
Entrance
warning
The keypad emits an intermittent beep
tone during entry delay periods to remind
the user to disarm the area.
Exit warning The keypad emits an intermittent beep
tone during exit delay.
Invalid button
buzz
When an invalid button, or sequence of
buttons, is pressed, the keypad emits a
at buzz tone.
Keypad
encoding tone
The keypad emits a muted beep tone as
each button is pressed to indicate that
the entry was accepted.
Trouble buzzer When a trouble event occurs, such as a
service alert, the keypad emits a two-tone
warble until you enter a programmed
passcode with the appropriate authority.
Watch tone A single clean tweedle tone alerts the
user anytime a watch point is faulted.
Table 6.1: Keypad audible tones
en Installation Guide
ATM Style Alphanumeric Keypad (SDI2)
B930