Daim Ntawv Qhia Tus Neeg Siv
73690900 / AQ251486498741en-0106052 | © Danfoss | DCS-SGDPT/SI | 2023.03
NovoCon® S - High Accuracy Actuator
ІМПОРТЕР:
UA: ТОВ з ІІ «Данфосс ТОВ», вул. Вікентія Хвойки, 15/15/6, м. Київ, 04080, Україна
NovoCon® S
Application mode:
MSV:9 / 32810
Digital control (default),
Analog control,
CO6 mode,
Inverted CO6 mode,
CO6 without alarms,
Inverted CO6 without alarms,
Analog CO6 mode,
Analog inverted CO6 mode
Select Valve Type
MSV:3 / 32802
(default AB-QM 4.0
ISO DN 15)
Design Flow Rate
AV:30 / 32796
Heating
AV:31 / 32798
Cooling
Select application
MSV:10 / 32811
Heating (default)
Cooling
Activate calibration
MSV:0 / 33284 state 2
or use manual
calibration
Terminal Nr. Description
18 Volume pulse output (+)
19 Ground (-)
19
18
SonoSensor 30Cable NovoCon® I/O
24 V
GND
GND
AI
AO
T1
T2
❽
E100 VXX
281624
0030471
E100 VXX
281624
0030471
MADE IN SLOVENIA
NovoCon
S
003Z8504
Actuator for AB-QM DN10-32
Control signal: BACnet MS/TP, Modbus RTU, 0-10V, 0-20mA
®
6430 Nordborg, Denmark
Power: 24VAC/DC, 50/60 HZ
Force: 90N. Stroke: 7 mm. Speed: 3-24s/mm
Consumption: 3.3VA running. Standby 0.9W
IP54/40, -10T55
III
01
E100 VXX
281624
0030471
01
01
Serial number and QR code can be removed from the
NovoCon® S label and added to installation drawing.
Device Object
Instance Number
Firmware update
We recommend to validate the firmware version before installation.
The latest firmware can be downloaded at www.novocon.com by selecting
the tab: Support files.
To avoid injury and damage to persons and devices, it is
absolutely necessary these instructions are carefully read and
observed prior to assembly and commissioning.
Necessary assembly, start-up, and maintenance work must be
performed only by qualified, trained and authorised personnel.
Switch off the power line before wiring the actuator.
Connect via safety isolating transformer.
Galvanic separations shall be provided for segments crossing buildings.
Safety Note
Safety Note
If the NovoCon® S network is supplied with two or more AC
power boosters, caution must be observed when disconnecting
one of the transformers from the high voltage power line. As the
NovoCons are connected in a daisy chain, there may be high
voltage on the primary side of the disconnected power supply. Disconnect
always both the primary and secondary side of the transformer.
Safety Note
❾ ❿
⓬
Initial configuration
DIP Switch
DIP Switches 1 to 7 are used to assign the MAC address manually.
Default MAC address assignment method is Auto MAC addressing for
BACnet MS/TP and DIP Switches for Modbus RTU.
For termination of last unit on the field bus, turn DIP Switch 8 ON.
Dip switch 9 is not used.
Dip switch 10 is used to select between BACnet MS/TP (OFF=Default)
and Modbus RTU (ON).
When the protocol is changed on DIP Switch 10, a power cycle is required.
1 2 3 4 5 6 7 8 9 10
ON
OFF
⓭